- Suitable for use in wet or dry areas
- Easy installation and retrofitting
- High flexibility
KSL double layer
Ablative mineral fibre board seal
Mixed penetration sealing system made of mineral fibre boards with an ablative coating for electrical installations, combustible / non-combustible pipes and other services
Fire Resistance Class
- maximum EI 120 in accordance with EN 13501-2
Field of Application
- Plasterboard wall
- Solid wall
- Floor
- Shaft wall
Certifications
- ETA-16/0320
- ETA-18/0885
- KB 321031804-A
Downloads
Datasheets
Application Data Sheet KSL double-layerInstallation manual
Installation Manual KSL double-layerProduct Features
System Data
Certificate of usability:
ETA-16/0320
Component thickness:
Wall ≥ 94 mm
Shaft wall ≥ 40 mm
Floor ≥ 150 mm
Sealing thickness:
Wall ≥ 100 mm
Floor ≥ 150 mm (2 Platten + Luftspalt)
Maximum sealing size:
Wall 1100 x 2200 mm
Shaft wall 800 mm x 600 mm
Floor 1000 mm x ∞
Allowed Services
Services | Max. Diameter |
Cables | ≤ 80 mm |
Cable bundle | ≤ 100 / ≤ 21 mm |
Cable trays | ✔ |
Coaxial cables and wave guides | ≤ 51, 1 mm |
EIR (single) | ≤ 63 / ≤ 21 mm |
EIR (bundled) | ≤ 100 / ≤ 63 / ≤ 21 mm |
Combustible pipes | ≤ 160 mm |
Multilayer pipes | ≤ 75 mm |
Non-combustible pipes with insulation made of mineral wool | ≤ 219,1 mm (steel) / ≤ 88,9 mm (copper) |
Non-combustible pipes with FEF insulation | ≤ 219,1 mm (steel) / ≤ 88,9 mm (copper) |
HVAC split line combinations | ✔ |
Related Products
Description | Package Sizes | Item No. |
BML fire stop compound | 5 kg pail 12,5 kg pail | 40050 40125 |
BMS fire stop filler | 5 kg pail 12,5 kg pail | 10500 10125 |
BMK filler | 0,4 kg cartridge | 30004 |
BSL mineral fibre board | pre-coated on one side with BML fire stop compound (dry film thickness = approx. 1.0 mm) Dimensions 100 x 625 x 50 mm | 50050 |
NBR-Plus fire protection wrap | Roll à 10 m x 125 mm (separable into 2x 62,5 mm) | 01261941 |
KSL-W fire protection wrap | Roll à 20 m x 50 mm self-adhesive Roll à 10 m x 100 mm self-adhesive | 15520 15530 |
Variant N II A fire protection collar | Ø 32–160 mm | 15032–15160 |
Variant N EC fire protection collar | 10 m fire protection wrap, 3 m metal strip, 18 hooks, 6 labels | 15103 |
CT Cable Tube | Ø 90 mm / L 300 mm Ø 120 mm / L 300 mm | 01279300 01281300 |