Your Request for

PYRO-SAFE<sup>®</sup> Novasit K2

PYRO-SAFE® Novasit K2

Fire protection mortar

Your Contact Data

* required
Back
PYRO-SAFE<sup>®</sup> Novasit K2

PYRO-SAFE® Novasit K2

Fire protection mortar


Fibre-free ready-mixed dry mortar of mortar group IIIa or M20. PYRO-SAFE® NOVASIT K2 is suitable for pumping, pressing and manual installation.

Einsatzbereiche Icon

Field of Application

  • Sealing joints around air conditioning and ventilation ducts, fire dampers, fire doors and shut-off devices.
  • Filling of cavities when installing steel frames.
  • Fire and smoke-proof sealing of individual cables (e.g. according to MLAR or other guidelines for easier cable routing).
verwendbarkeitsnachweis Icon

Certification

  • DoP No. 0116300-NOVASIT-K2
Anwendung im System Icon

Used for system

PYRO-SAFE® CT - Fire stop system
https://svt-global.com/applications/pyro-safe-ct-fire-stop-system

Field of Application

Fire protection mortar (Fire behaviour class A1 according to DIN EN 998-2). Universally applicable within the range of massive walls and floors for:

  • penetrations of isolated metallic pipe
  • fire- and smoke-resistant sealing of single lines according to MLAR
  • joints around climatic and air ducts, fire dampers, fire protection doors, valves
  • filling the voids of door steel frames

Applicability certificate

Tested and approved according to national and international standards as e.g.:
DIN, EN, other standards on request

Product Features

One-component, hydraulically hardening; applied by spraying, pressing and manual installation; free from fi bres, phenols and halogens, ageing resistant.

Handling

  • Application temperature > +5 °C
  • Application time app. 2 – 3 hours
  • Fully cured time app. 28 days
  • Surfaces must be firm and free from adhesion-reducing substances and dust. Absorbent surfaces are to be pre-wetted with water.
  • The consistency of the mortar has to be adjusted in such a way that all openings are cavity-free filled.

Technical Data

Color grey
Gross density (wet mortar) 2.000 kg/m³ ± 100 kg/m³
Gross density (dry mortar) 1.75 – 1.85 kg/dm³
Pressure resistance ≥ 20 N/mm² (M 20)
Consumption
4.0 – 4.5 l water + 25kg dry mortar
≈ 15 l ready-to-use wet mortar
≈ 15 l volumes after curing time