Certificate of usability:
ETA-22/0051
Thickness structural element:
Wall ≥ 150 mm
Floor ≥ 150 mm
Sealing thickness:
Wall ≥ 150 mm
Floor ≥ 150 mm
Maximum sealing size:
Wall 1200 x 2000 mm
Floor 1200 x 2000 mm
Mixed penetration seal
Mixed penetration sealing system made of fire protection compound for various services.
Certificate of usability:
ETA-22/0051
Thickness structural element:
Wall ≥ 150 mm
Floor ≥ 150 mm
Sealing thickness:
Wall ≥ 150 mm
Floor ≥ 150 mm
Maximum sealing size:
Wall 1200 x 2000 mm
Floor 1200 x 2000 mm
Services | Maximum diameter |
Cables | ≤ 80 mm |
Cable bundles | ≤ 100 / ≤ 21 mm |
Cable trays | without restrictions |
EIC (single) | ≤ 63 / ≤ 21 mm (≤ 100 / ≤ 50 mm in floors) |
EIC (bundled) | ≤ 100 / ≤ 32 / ≤ 21 mm |
PE-lines „speed pipes“ | 24x ≤ 7.0 mm 7x ≤ 10.0 mm 5x ≤ 12.0 mm |
Combustible pipes | ≤ 160 mm |
Multilayerpipes | ≤ 63 mm |
Noncombustible pipes with insulation made of mineral fibre |
≤ 323.9 mm (steel) ≤ 88.9 mm (copper) |
Noncombustible pipes with insulation made of FEF |
≤ 168.3 mm (steel) ≤ 108 mm (copper) |
HVAC split-line-combinations | ✔ |