PYRO-SAFE® Novasit BM

PYRO-SAFE® Novasit BM

Fire resistance max. EI 120 acc. EN 13501-2

Mixed penetration sealing system made of fire protection compound for various services

System Data

Certificate of usability:
ETA-16/0132

Thickness structural element:
Wall ≥ 150
Floor ≥ 150

Sealing thickness:
Wall ≥ 150
Floor ≥ 150

Maximum sealing size:
Wall 1200 x 2000
Floor 1200 x 2000

(Dimensions in mm)

Field of application

Solid wall, floor

Allowed services (Dimensions in mm)

Services Maximum diameter
Cables ≤ 80
Cable bundles ≤ 100 / ≤ 21
Cable trays without restrictions
EIC (single) ≤ 63 / ≤ 21
(≤ 100 / ≤ 50 in floors)
EIC (bundled) ≤ 100 / ≤ 32 / ≤ 21
PE-lines „speed pipes“ 24x ≤ 7.0
7x ≤ 10.0
5x ≤ 12.0
Combustible pipes ≤ 160
Multilayerpipes ≤ 63
Noncombustible pipes with
insulation made of mineral fibre
≤ 323.9 (steel)
≤ 88.9 (copper)
Noncombustible pipes with
insulation made of FEF
≤ 168.3 (steel)
≤ 108 (copper)
HVAC split-line-combinations

Products