Colour | anthracite, on request | |
Density (+20°C) | 1,080 – 1,320 g/cm³ | |
Viscosity (+20°C) | 6,000 – 10,000 mPas (at +20°C) (thixotropic) | |
Temperature resistance | -20°C to +80°C (tested 40 days without mechanical stress) | |
Reaction temperature | 150°C | |
Volatile components (VOC) | The VOC content is well below the smallest limit of 50 g/L set by GS-11 (Green Seal Standard, issue 3.1/2013). | |
Application temperature | +5°C to +30°C | |
Application (min. +5°C / < 85 % relative humidity) | Application is preferably by airless (nozzle orifice ≥ 0.051 inch = 1.3 mm) or compressed air painting (nozzle orifice ≥ 3.5 to ≤ 4 mm) at temperatures ≥ 5°C and ≤ 85 % relative humidity. PYRO-SAFE® B CX 1200 can be adjusted with water to the preferred processing viscosity. | |
Drying time | Ambient conditions +25°C/35 % relative humidity +80°C/35 % relative humidity | Wet film thickness 500 μm Can be painted over with itself after approx. 30 min after approx. 10 min |
Example consumption | Solids (wt.) 65 – 75 % Application quantity [g/m²] 500 g/m2 / 1,000 g/m2 | Layer thickness [μm] Wet 550 μm / 1,100 μm Layer thickness [μm] Dry 300 μm / 600 μm* |
Storage | At room temperature (+5°C to +30°C), exceeding the ambient temperature by up to 10°C < 12 hours is unproblematic. Protect from frost. 18 months in sealed original container. | |
Safety information | PYRO-SAFE® B CX 1200 is not a hazardous substance according to the German Ordinance on Hazardous Substances (GefStoffV) and not a dangerous good according to the German Ordinance on Dangerous Goods (GGVS/ADR). Further information can be found in the safety data sheet. |
*The required dry film thickness varies depending on the fire protection requirements and fire protection properties of the structures to be protected. Splash losses are not taken into account!