Radiation protection mortar for filling openings of cable and pipe penetrations in floors and walls, also suitable as filling material for door frames. To be used in nuclear installations, reprocessing plants and plants with radiation protection requirements in accordance with radiation protection regulation (StrlSchV) and Roentgen regulation (RöV).
Nuclasit 2.4
Fire & radiation protection mortar
One-component, hydraulically curing and ageing-resistant, suitable for pumping, pressing and for manual installation, free of fibres, phenol and halogen softeners
Field of Application
- Use in nuclear installations, reprocessing plants and machines with radiation protection requirements according to the German Radiation Protection Act (StrlSchV) and X-ray Act (RöV)
- Used as closure material for cable, pipe and mixed penetration seals
Certification
- DoP No. 01165000-NUCLASIT-2.4
Downloads
Datasheets
Technical Data Sheet NUCLASIT 2.4Safety datasheets
Safety Data Sheet NUCLASIT 2.4Declaration of performance
Declaration of performance - NUCLASIT 2.4Field of Application
Applicability certificate
Tested and approved according to national and international standards as e.g.:
DIN V 18580 and DIN EN 998-2, other standards on request
Product Features
One-component, hydraulically hardening; applied by spraying, pressing and manual installation; free from fibres, phenols and halogens, aging resistant.
Radiology
No radiation-induced damages of serious kind determined according to irradiation table (stage 3 and stage 4) during the irradiation with gamma-rays.
Attenuation measurement
Attenuation measurements accomplished at insulating boards made of mineral mortar NULASIT 2.4 (plates 55 x 55 x 5 cm). The shield effect of the insulating boards is comparable with Barite concrete with a density of 3.5 g/cm³.
Pressure resistance examination
The determined pressure resistances according to DIN 18550 of unirradiated and irradiated radiation protection mortar NUCALSIT 2.4 is comparable.
Handling
- Application temperature > +5 °C
- Processing time app. 3 – 4 hours
- Ultimate strength and setting-off reached after app. 28 days
- Surfaces must be firm and free from adhesion-reducing substances and dust.
Absorbent surfaces are to be pre-wetted with water. - The consistency of the mortar has to be adjusted in such a way that all openings are cavity-free filled.
Technical Data
Color | reddish-grey |
Gross density (wet mortar) | 2,800 – 3,100 kg/m³ |
Gross density (dry mortar) | 2.50 – 2.9 kg/dm³ |
Pressure resistance | 18 – 22 N/mm² |
Bond strength |
0.5 – 0.8 N/mm² |
Compression strength within the mortar joint |
3 – 4 N/mm² |
Consumption |
~ 3l water + 30kg dry mortar ≈ 11l ready-to-use wet mortar ≈ 11l volumes after curing time |