PYRO-SAFE® CT

Fire stop system

Easy-to-build penetration sealing system with snap-on lock comprising of two half shells with inner lining of fire protection fabric.

Downloads

System Data

Certificate of usability:
ETA-16/0016

Thickness structural element:
Wall ≥ 100 mm
Floor ≥ 125 mm

Sealing thickness:
Wall ≥ 150 mm
Floor ≥ 150 mm

Maximum sealing size:
Wall 1.200 x 2.000 mm
Floor 640 x ∞ mm

Fire resistance

max. EI 120 acc. EN 13501-2

Field of application

Plasterboard wall, solid wall, floor

Allowed Services

Services Maximum diameter
Cables ≤ 80 mm
Cable bundles ≤ 107 / ≤ 21 mm
EIC (single) ≤ 63 / ≤ 21 mm
EIC (bundled) ≤ 107 / ≤ 32 / ≤ 21 mm
PE-lines „speed pipes“ 24x ≤ 7.0 mm
7x ≤ 10.0 mm
5x ≤ 12.0 mm
Combustible pipes ≤ 32 mm
HVAC split-line-combinations

Products